The derivation of all of the tables and charts for voltage drop calculations is:
CM = (K x I x L)/E
where:
CM = area of conductor in circular mils
K = 10.75, a constant representing the resistivity of copper
L = circuit length in feet
E = maximum allowable voltage drop, at load, in volts (e.g.; 3% voltage drop in a 72VDC system would be 6.97VDC)
Note that this formula does not take into account the loss of heat transfer capability from an individual conductor as a result of bundling the conductors or running them in a conduit or chase.
Hope this helps.
Charlie