http://m.campingworld.com/shopping/item/110v-electrical-power-outlet-box-30-amp/20811
You need to install a 30a breaker in your power distribution panel, then a proper 30a receptacle fed from the breaker with appropriately sized wire. The sum total current rating should not exceed your main breaker. No, don't try to use one leg of a 220v circuit. It won't give you anything but trouble. You really need to have a licensed electrician come in and do it. It is probably illegal for you to do this yourself and an electrician will do everything to code and give you a safe installation.